The BKN series canned pump is a hot/cold water canned circulator. Its hydraulic part consists of the pump casing and impeller: the casing is HT200 cast iron and the impeller is PPO modified engineering plastic / stainless steel. The motor has a built-in thermal protector that cuts the circuit when the winding temperature exceeds the limit and restarts the motor when the temperature falls back - safe and reliable. For circulation duty in domestic central hot-water, air-source and solar systems.
From the manual (Chinese): introduction, working conditions and dimensions
● Canned construction: sealless, leak-free, quiet and low energy consumption
● HT200 cast iron casing; PPO / stainless steel impeller, corrosion resistant
● Built-in motor thermal protection with automatic restart
● 13 models: EH single-phase 220 V, QH three-phase 380 V; 320-1950 W, max. flow 5-28 m3/h, max. head 16-32 m, ports 25-50 mm
| Model | Supply | Input W | Current A | Max head m | Max flow m3/h | Rated head m | Rated flow m3/h | Port mm | Weight kG | Pressure bar |
| BKN-201EH | 1~220V 50Hz | 320 | 1.5 | 16 | 5 | 10 | 3 | 25 | 7 | 5 |
| BKN-402EH | 1~220V 50Hz | 720 | 3.2 | 23 | 6.5 | 16 | 4 | 32 | 10 | 5 |
| BKN-403EH | 1~220V 50Hz | 660 | 3.2 | 23 | 6.5 | 16 | 4 | 25 | 10 | 5 |
| BKN-601EH | 1~220V 50Hz | 880 | 4 | 28 | 7.5 | 20 | 4 | 25 | 11.5 | 5 |
| BKN-750EH | 1~220V 50Hz | 1100 | 5.1 | 26 | 12 | 18 | 6.6 | 32 | 12.5 | 4 |
| BKN-751EH | 1~220V 50Hz | 1250 | 6 | 32 | 7.5 | 20 | 5 | 32 | 13 | 4 |
| BKN-1100EH | 1~220V 50Hz | 1500 | 7.2 | 30 | 16 | 23 | 8 | 40 | 19 | 4 |
| BKN-1500EH | 1~220V 50Hz | 1950 | 10 | 24 | 28 | 20 | 16 | 50 | 21 | 4 |
| BKN-601QH | 1~380V 50Hz | 880 | 4 | 28 | 7.5 | 20 | 4 | 25 | 11.5 | 5 |
| BKN-750QH | 1~380V 50Hz | 1100 | 5.1 | 26 | 12 | 18 | 6.6 | 32 | 12.5 | 4 |
| BKN-751QH | 1~380V 50Hz | 1250 | 6 | 32 | 7.5 | 20 | 5 | 32 | 13 | 4 |
| BKN-1100QH | 1~380V 50Hz | 1500 | 7.2 | 30 | 16 | 23 | 8 | 40 | 19 | 4 |
| BKN-1500QH | 1~380V 50Hz | 1950 | 10 | 24 | 28 | 20 | 16 | 50 | 21 | 4 |
From the manual (Chinese): data table and performance curves
From the manual (Chinese): maintenance and troubleshooting
● Ambient temperature 0-40 C, liquid temperature 0-90 C, altitude <1000 m
● Circulation for domestic central hot-water systems, air-source heat pumps, solar systems and similar
● Warranty: one year for non-man-made faults under normal use
Contact: Peter