  • burks S330 Pump-Dedicated Variable Frequency Drive
burks S330 Pump-Dedicated Variable Frequency Drive

burks S330 Pump-Dedicated Variable Frequency Drive

  • Product description: burks S330 pump-dedicated frequency inverter features water-industry-specific current vector control and constant pressure accuracy of 0.01MPa. It supports multi-pump networking, main/auxiliary pump c
  • INQUIRY

USER MANUAL

Tap or scan
to view on phone
Online preview

Product Overview

The S330 is a current vector inverter dedicated to the water industry, designed for constant pressure water supply with a constant pressure accuracy of 0.01MPa. It can efficiently drive induction motors and synchronous motors, supports multi-pump networking and main/auxiliary pump control (panel indicator A shows main/auxiliary status), and the power-on auto-start function is enabled by default.

Technical Parameters

Control mode Open-loop vector control (SVC), closed-loop vector control (FVC), V/F control
Maximum frequency Vector control 0~300Hz; V/F control 0~3200Hz
Carrier frequency 0.5kHz~15kHz, automatically adjustable according to load characteristics
Starting torque 0.5Hz / 110%
Speed control range 1:100 (SVC), 1:1000 (FVC)
Speed stability accuracy ±0.5% (SVC), ±0.02% (FVC)
Constant pressure accuracy 0.01MPa
Torque control accuracy ±5% (FVC)
Jog control Jog frequency range 0.00Hz~50.00Hz
Automatic voltage regulation (AVR) Automatically maintains constant output voltage when grid voltage changes
Panel indicators READY (power/alarm), RUN (run/stop), COM (communication indicator), SENSOR (sensor indicator), and A (main/auxiliary), M (manual), C (speed mode) status indicators

Application Scope

Constant pressure water supply systems, inverter retrofit of water supply pumps, and one-duty-one-standby and multi-pump linked water supply units. Please consult and confirm the applicable power and voltage specifications according to the motor nameplate; installation, wiring, and parameter settings should be performed by professionals.

Operating Environment

Ambient temperature -10℃~+50℃
Humidity Less than 95%RH (non-condensing)
Vibration Not more than 0.6G, keep away from punch presses and similar equipment
Protection requirements Prevent ingress of water droplets, steam, dust, fine metal powder, oil, salt, and corrosive gases; keep away from electromagnetic interference sources
Prohibited environments Do not use in hazardous environments with flammable, combustible, explosive gases, liquids, or solids

Common Fault Codes

Code Fault Common Causes and Troubleshooting
Err.01P Undervoltage fault Instantaneous power failure, input voltage out of specified range, abnormal bus voltage; reset the fault, adjust voltage to normal range
Err.02P Overvoltage during acceleration Input voltage too high, acceleration time too short; adjust voltage to normal range, increase acceleration time
Err.03P Overcurrent during deceleration Output circuit grounded or short-circuited, deceleration time too short, voltage too low; eliminate peripheral faults, increase deceleration time
Err.04P Overcurrent at constant speed Output circuit grounded or short-circuited, sudden load increase during operation, undersized selection; eliminate peripheral faults, select a higher power rating
Err.05P Overcurrent during acceleration Acceleration time too short, inappropriate V/F curve, voltage too low; increase acceleration time, adjust torque boost or V/F curve
Err.06P Overvoltage during deceleration Input voltage too high, deceleration time too short; adjust voltage to normal range, increase deceleration time
Err.07P Motor overload Undersized selection, excessive load, or motor stall; reduce load and check motor and mechanical conditions
Err.08P Inverter overload Undersized selection, excessive load, or motor stall; select an inverter with a higher power rating
Err.09P Inverter unit protection Output circuit short-circuited, module overheated, internal wiring loose; eliminate peripheral faults, check air duct and fan
Err.10P Control power supply fault Input voltage out of specified range; adjust voltage to within the specified range
Err.12P Output phase loss Abnormal wiring from inverter to motor, three-phase output unbalanced; eliminate peripheral faults, check motor three-phase windings
Err.20P Input phase loss Abnormal three-phase input power, abnormal surge protection board or main control board; check and eliminate peripheral circuit problems

When fault handling involves wiring and internal components, please contact professionals.